Answer by Retired Master Electrician for 60V Hot to onward neutral
When you disconnected all of the neutral wires.You changed the configuration of the circuit. Basically all circuits in the US are wired in parallel. When you disconnected the neutrals you change that...
View ArticleAnswer by Harper - Reinstate Monica for 60V Hot to onward neutral
Sounds like you have a neutral - ground-fault somewhere on that branch. It has about the same impedance as your tester.
View Article60V Hot to onward neutral
I have an outlet with three sets of wires coming into it. One set is carrying the power (from an upstream outlet) and two others are connected to downstream outlets. I first disconnected all of the...